For conductors with large cross-sectional area (CSA), GKONCY ELECTRIC offers spring-cage terminals with the CSA from 10 mm2 to 35 mm2. The double-row bridge allows chain bridging and conversion bridging, such as those with the CSA from 2.5 mm2 to 4 mm2. The application of the RB conversion bridgeware can easily perform voltage supply and division.
For conductors with large cross-sectional area (CSA), GKONCY ELECTRIC offers spring-cage terminals with the CSA from 10 mm2 to 35 mm2. The double-row bridge allows chain bridging and conversion bridging, such as those with the CSA from 2.5 mm2 to 4 mm2. The application of the RB conversion bridgeware can easily perform voltage supply and division.
Rigid solid
Flexible multi-conductor
I
Ui
(mm2)
(A)
(V)
IEC 60947-7-1
1.5-16
1.5-10
65
800
Description
Color
Schematic diagram
Type
Spring-cage terminal mounted on
Grey
JWD2-10a
Blue
JWD2-10a BU
(1) End plate
Grey
G-D2-10a
(2) Plug-in bridgeware used for horizontal connection in the terminal center
2 digits
FBS2-10
lmax:57A
(3) Conversion bridgeware for connecting JWD2-6a to JWD2-2.5a or JWD2-4a
RB 10-(2.5/4)
lmax:55A
(4) Warning panel mounted at the operation port of the JWD2 "Miniature Spring" spring-cage terminal
WST10
(5) Screwdriver
SZF 3-1.0X5.5
(6) Quick tag, with 10 digits for identification in the terminal center
White
ZP10
(7) Quick designation strip, with 100 digits for lateral identification
White
ZBFM8
(8) Test plug
Grey
Terminal dimensions
Thickness / length / end plate thickness
[mm]
10/71.5/2.2
Height (TH 35:7.5 / TH 35:15)
[mm]
50.5/58
Technical data in accordance with IEC/DIN VDE standards
Maximum rated working current / cross-sectional area
[A] / [mm2]
65/16
Rated impulse withstand voltage / degree of pollution
[KV] / -
8/3
Over-voltage category / insulation material group
- / -
lll/l
Connection
Stranded wire with tubular pre-insulated terminal
[mm2]
1.5-10
Stranded wire with tubular bare terminal
[mm2]
1.5-10
Stripping length
[mm]
18
Plug gauge (IEC60947-1)
A6
Insulation material
PA
Grading as per UL 94
V0
Certification data (UL and CSA/CUL)
Rated working voltage / rated working current / wire gauge