For power distribution, the application of the three-conductor spring terminal JWD2.../1-2 can greatly save the space and costs.
Actually, one terminal is usually required to connect three conductors. The terminal (/1-2) can connect three conductors without any additional terminals or bridgeware.
The connection mode of the general-purpose FBS plug-in bridgeware can achieve horizontal connection of adjacent straight-way terminals.
For power distribution, the application of the three-conductor spring terminal JWD2…/1-2 can greatly save the space and costs.
Actually, one terminal is usually required to connect three conductors. The terminal (/1-2) can connect three conductors without any additional terminals or bridgeware.
The connection mode of the general-purpose FBS plug-in bridgeware can achieve horizontal connection of adjacent straight-way terminals.
Rigid solid
Flexible multi-conductor
I
Ui
(mm2)
(A)
(V)
IEC 60947-7-1
0.14-1.5
0.14-1.5
17.5*
500
* The total current of all connections should not exceed the maximum load current.
Terminal dimensions
Thickness / length / end plate thickness
[mm]
16/100/-
Height (TH 35:7.5 / TH 35:15)
[mm]
59/66.5
Technical data in accordance with IEC/DIN VDE standards
Maximum rated working current / cross-sectional area
[A] / [mm2]
115/35
Rated impulse withstand voltage / degree of pollution
[KV] / -
8月3日
Over-voltage category / insulation material group
- / -
III/I
Connection
Stranded wire with tubular pre-insulated terminal
[mm2]
2.5-35
Stranded wire with tubular bare terminal
[mm2]
2.5-35
Stripping length
[mm]
25
Plug gauge (IEC60947-1)
A8
Insulation material
PA
Grading as per UL 94
V0
Certification data (UL and CSA/CUL)
Rated working voltage / rated working current / wire gauge
UL: [V]/[A]/AWG
-
CSA/CUL: [V]/[A]/AWG
-
Terminal dimensions
Thickness / length /end plate thickness
[mm]
4.2/60.5/2.2
Height (TH 35:7.5 / TH 35:15)
[mm]
36.5/44
Technical data in accordance with IEC/DIN VDE standards
Maximum rated working current / cross-sectional area
[A] / [mm2]
17.5/1.5
Rated impulse withstand voltage / degree of pollution
[KV] / -
6/3
Over-voltage category / insulation material group
- / -
lll/l
Connection
Stranded wire with tubular pre-insulated terminal
[mm2]
0.25-1.5
Stranded wire with tubular bare terminal
[mm2]
0.25-1.5
Stripping length
[mm]
10
Plug gauge (IEC60947-1)
A1
Insulation material
PA
Grading as per UL 94
V0
Certification data (UL and CSA/CUL)
Rated working voltage / rated working current / wire gauge