Terminal thickness: 25 | ||||
Rigid conductor | Flexible conductor | I | Ui | |
(mm2) | (A) | (V) | ||
IEC 60947-7-1 | 25-95 | 35-95 | 232 | 1000 |
Products Category
JWD1-95 Screw Type High-Current Din-Rail TB
Product Description
Parameters
Certification
Description | Color | Type |
Terminal: With general-purpose locating base, suitable for standard mounting rails |
Grey | JWD1-95 |
Blue | JWD1-95 BU | |
Yellow-green | ||
(1) Central liaison part: It is used to connect terminals with the same specification and form a liaison terminal group; the divider on the terminal housing must be removed. |
2 digits | |
3 digits | ||
(2) Edge liaison part: Its role is the same as that of the central liaison part (1); with insulation on the back side, inserted in the conductor holder, and clamped on the insulation housing of the terminal |
2 digits | BL 25/2 |
3 digits | BL 25/3 | |
(3) Prismatic conductor holder: A prismatic metal block used to compensate the pressed flat conductor |
95 EP | |
(4) Warning sign: Attached to the surface on top of the terminal |
||
(5) Tag: It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will). |
ZP10 | |
(6) Terminal fastener: (thickness: 10) It is used to finally fix a large-current terminal; after it is pushed, it can be mounted on Type TH35/15 mounting rail, and it should be fixed with two screws. |
ZG2 |
Terminal dimensions | ||
Thickness / width / end plate thickness | [mm] | 25/83 |
Height (TH 35:7.5 / TH 35:15 / G 32:15) | [mm] | 97.5/95.5 |
Technical data based on IEC/DIN VDE standards | ||
Maximum rated working current / cross-sectional area | [A] / [mm2] | 232/95 |
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is used: | [mm2] | 95/70 |
Rated impulse withstand voltage / degree of pollution | [kV]/- | 45507 |
Over-voltage category / insulation material group | -/- | III/I |
Connection capacity | ||
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal | [mm2] | 35-95/36-95 |
Connection of multiple conductors (two conductors with the same cross-sectional area) | ||
Rigid conductor / flexible conductor | [mm2] | 25-35/25-35 |
Flexible conductor with tubular bare terminal | [mm2] | 16-35 |
Stripping length | [mm] | 33 |
Screw type | M8* | |
Torque | [Nm] | 15-20 |
Insulation material type | PA | |
Material flammability according to UL94 | V0 | |
Rated working voltage / rated working current / wire gauge | UL: [V]/[A]/AWG | 600/230/2-4/0 |
*) Socket head cap screw |
• Excellent thermal stability: continuous operation at the ambient temperature of 100 °C; resistant to a high temperature up to 200 °C for a short period |
• High heat resistance class: the product is non-flammable, and its flame retardant rating is Grade UL94V-C; |
Welcome to consult us for more information!