Terminal thickness: 8 Miniature current terminal | ||||||
Rigid conductor | Flexible conductor | I | Ui | |||
(mm2) | (A) | (V) | ||||
0.2-10 | 0.2-6 | 57 | 500 | |||
IEC 60947-7-1 | ||||||
Type | Part Number | Package quantity |
Products Category
JWD1-6T Screw Type Switching TB for Breaking Capacity
Product Description
Parameters
Certification
Description | Schematic diagram | Type | |||
Test terminal: | JWD1-6T | ||||
With general-purpose locating base, suitable for standard mounting rails | |||||
and | |||||
Switching terminal: | |||||
With general-purpose locating base, suitable for standard mounting rails | |||||
and | |||||
(1) End plate: | |||||
One additional piece must be attached to the end of each terminal strip set. If it is mounted in the center of the terminal strip, the creepage distance may increase. | |||||
(2) Central liaison part: | JWD9-ZL 8/2 | ||||
It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will. | JWD9-ZL 8/3 | ||||
JWD9-ZL8/4 | |||||
JWD9-ZL8/10 | |||||
(3) Edge liaison part | 2 digits: | JWD9-BL 8/2 | |||
Its role is the same as that of the central liaison part (2); with insulation on the back side; 10 digits that can be further divided at will | JWD9-BL 8/3 | ||||
JWD9-BL8/4 | |||||
JWD9-BL8/10 | |||||
3 digits: | |||||
10 digits: | |||||
(4) Divider: | |||||
It is used to separate two adjacent liaison terminal groups and can be inserted after assembly, without any effect on the overall space. | |||||
(5) Group partition: | |||||
Used for separation of each terminal group; with dual effects (visible grouping and electrical isolation) | |||||
(6) Central liaison part | JWD9-LJ 8/2 | ||||
It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will. | |||||
(7) Switch liaison part | |||||
It can be used on both sides of the breaking sliding block for two terminals; the strap of the liaison part is pushed inwards to make it break; two screws are supplied. | |||||
(8) Switch liaison part | |||||
It can be used on both sides of the breaking sliding block for two terminals; the strap of the liaison part is pushed outwards to make it break; two screws are supplied. | |||||
(9) Switch liaison part | |||||
It is used for two terminals; please note that it can only be used on the right of terminals; two screws are supplied. | |||||
(10) Switch liaison part | |||||
It is used for the short circuit of a three-phase interconnected current transformer and can only be used on the right of the terminal; 1) four screws are supplied. | |||||
(11) Test plug: | ZP9.5/8-10 | ||||
(12) Conversion test plug: | |||||
(13) Tag: |
Terminal dimensions | |||
Thickness / width / end plate thickness | [mm] | 8/51.2/- | |
Height (TH 35:7.5 / TH 35:15 / G 32:15) | [mm] | 46/53.5/- | |
Technical data based on IEC/DIN VDE standards | |||
Maximum rated working current / cross-sectional area | [A]/ [mm] | Jun-57 | |
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is used | [mm2] | 6月6日 | |
Rated impulse withstand voltage / degree of pollution | [kV]/- | 6月3日 | |
Over-voltage category / insulation material group | -/- | lll/l | |
Connection capacity | |||
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal | [mm2] | 0.5-6/0.5-4 | |
Connection of multiple conductors (connecting two conductors with the same cross-sectional area) | |||
Rigid conductor / flexible conductor | [mm2] | 0.5-2.5/0.5-6 | |
Flexible conductor with tubular bare terminal | [mm2] | 0.5-4 | |
Flexible conductor with DEV-tubular pre-insulated terminal | [mm2] | 0.5^ | |
Stripping length | [mm] | 12 | |
Screw for terminal position: screw / torque | [Nm] | M4/1.5-1.8 | |
Screw for breaking sliding block: screw / torque | [Nm] | - | |
Insulation material type | PA | ||
Material flammability according to UL94 | V0 | ||
Rated working voltage / rated working current / wire gauge | UL:[V]/[A]/AWG | 300/50/26-8 |
Welcome to consult us for more information!