Terminal thickness: 8.2 | |||||
Rigid conductor | Flexible conductor | I | Ui | ||
(mm2) | (A) | (V) | |||
IEC 60 947-7-3 Used as a terminal for breaking capacity | 0.2-4 | 0.2-4 | 6.3* | 800 | |
With fuse | 0.2-4 | 0.2-4 | Note 1) |
Products Category
JWD1-6RD Screw Type Fuse Din-Rail TB
Product Description
Parameters
Certification
Description |
Schematic diagram |
Type |
Part Number |
Package quantity |
|||||
This fuse terminal can be mounted on the standard mounting rails and and can be equipped with a fuse tube (see Page 43 for details). |
|
JWD1-4RD (R055) |
5 574 141 |
25 |
|||||
Terminal with indicator lamp: (the same function as above) |
Voltage (AC / DC) |
Current |
|
|
|
||||
Terminal with indicator lamp: (the same function as above) |
24V-48V-110V, common for AC / DC |
2-3mmA |
JWD1-4RD/24V-110V AC/DC |
5 574 143 |
25 |
||||
Terminal with indicator lamp: (the same function as above) |
5V-12V, common for AC / DC |
1.8-9mmA |
JWD1-4RD/5V-12V AC/DC |
5 574 145 |
25 |
||||
Terminal with indicator lamp: (the same function as above) |
220V-380V, common for AC / DC |
1.6-4mmA |
JWD1-4RD/220V-380V AC/DC |
5 574 184 |
25 |
||||
(1) Central liaison part: It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will. |
|
|
|
|
|||||
(2) Connecting sheet For central connection of more than 10 digits |
|
|
|
|
|||||
(3) Edge liaison part: Its role is the same as that of the central liaison part; with insulation on the back side; 10 digits that can be further divided at will |
2 digits: |
|
BLS 8/2 |
8 582 182 |
100 |
||||
|
3 digits: |
|
BLS 8/3 |
8 582 183 |
100 |
||||
|
10 digits: |
|
BLS 8/10 |
8 582 190 |
50 |
||||
(4) Connecting strip: Used for coupling linkage of the hinge break-away arm |
|
4RD/LT |
8 824 101 |
|
|||||
(5) Tag: It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will). |
White |
|
ZP8 |
8 868 104 |
100 |
||||
Terminal dimensions |
|
|
|||||||
Thickness / width / end plate thickness |
[mm] |
8.2 / 72.5 |
|||||||
Height (TH 35:7.5 / TH 35:15 / G 32:15) |
[mm] |
56.5/64/61.5 |
|||||||
Technical data based on IEC/DIN VDE standards |
|
|
|||||||
Fuse type / dimensions & specifications |
-/ [mm] |
(See Page 42 for details.) |
|||||||
Maximum power consumption at 23 °C based on the E DIN VDE 0611-6: 1995-05 standard |
|
Note 1) |
|||||||
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is used |
[mm2] |
4/4 |
|||||||
Rated impulse withstand voltage / degree of pollution |
[kV]/- |
6/3 |
|||||||
Over-voltage category / insulation material group |
-/- |
III /1 |
|||||||
Connection capacity |
[mm2] |
|
|||||||
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal |
|
0.25-4 / 0.25-4 |
|||||||
Connection of multiple conductors (connecting two conductors with the same cross-sectional area) |
[mm2] |
|
|||||||
Rigid conductor / flexible conductor |
[mm2] |
0.2-4/0.2-4 |
|||||||
Flexible conductor with tubular bare terminal |
[mm2] |
0.25-4 |
|||||||
Flexible conductor with DEV-tubular pre-insulated terminal |
[mm] |
0.5-2.5 |
|||||||
Stripping length |
|
8 |
|||||||
Screw type |
[Nm] |
M3 |
|||||||
Torque |
[mm] |
0.6-0.8 |
|||||||
Insulation material type |
|
PA |
|||||||
Material flammability according to UL94 |
|
V0 |
|||||||
Rated working voltage / rated working current / wire gauge |
UL:[V]/[A]/AWG |
800/6.3/26-10 |
|||||||
Type G cartridge fuse-link with cylindrical cap ("Fuse Tube" for short) Fuse terminals with indicator lamp for special voltages can be customized upon the customer's request. |
|
Note 1): Current subject to the fuse tube, and voltage subject to the indicator lamp |