Terminal thickness: 20 | ||
Rigid conductor | Flexible conductor | |
(mm2) | ||
IEC 60947-7-2 | 16-50 | 25-50 |
Products Category
JWD1-50JD Screw Type High-Current Din-Rail TB
Product Description
Parameters
Certification
Description | Type | |
Ground Terminal: The yellow-green insulating housings can be mounted on the mounting rails |
JWD1-50 JD | |
Edge liaison part: Its role is the same as that of the central liaison part (2); with insulation on the back side; 10 digits that can be further divided at will |
2 digits: | |
3 digits: | ||
10 digits: | ||
Edge liaison part: Its role is the same as that of the central liaison part; with insulation on the back side, inserted in the conductor holder, and clamped on the insulation housing of the terminal |
2 digits | |
3 digits | ||
Prismatic conductor holder: A prismatic metal block used to compensate the pressed flat conductor |
50 EP | |
Terminal fastener: (thickness: 10) It is used to finally fix a large-current terminal; after it is pushed, it can be mounted on Type TH35/15 mounting rail, and it should be fixed with two screws. |
ZG2 | |
Tag: It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will); it is white. |
ZP10 |
Terminal dimensions | ||
Thickness / width / end plate thickness | [mm] | 20/70.5 |
Height (TH 35:7.5 / TH 35:15 / G 32:15) | [mm] | 83.5/81.5 |
Technical data based on IEC/DIN VDE standards | ||
Maximum rated working current / cross-sectional area | [A] / [mm2] | 150/50 |
Rated impulse withstand voltage / degree of pollution | [kV]/- | 8/31) |
Over-voltage category / insulation material group | -/- | III/I |
Connection capacity | ||
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal | [mm2] | 25 -50 / 25-50 |
Connection of multiple conductors (two conductors with the same cross-sectional area) | ||
Rigid conductor / flexible conductor | [mm2] | 10-16/10-16 |
Flexible conductor with tubular bare terminal | [mm2] | 45581 |
Flexible conductor with DEV-tubular pre-insulated terminal | [mm2] | - |
Stripping length | [mm] | 24 |
Screw for terminal position: screw type / torque | -/[Nm] | M 6*/ 6-8 |
Central fastening screw: screw type / torque | -/[Nm] | M 6*/ 6-8 |
Insulation material type | PA | |
Material flammability according to UL94 | V0 | |
Rated working voltage / rated working current / wire gauge | UL:[V]/[A]/AWG | -/-/6-1/0 |
Note: When an edge liaison part is used, a cable below 1.5 mm2 should be used for a 2.5 mm2 terminal; corresponding cables should be used for terminals with other cross-sectional areas (mm2). |
Welcome to consult us for more information!