Terminal thickness: 6.2 | ||||
Rigid conductor | Flexible conductor | I | Ui | |
(mm2) | (A) | (V) | ||
IEC 60947-7-1 | 0.2-6 | 0.2-4 | 41 | 800 |
Products Category
JWD1-4 Screw Type General Din-Rail TB
Product Description
Parameters
Certification
Description | Color | Type | |
Terminal: With general-purpose locating base, suitable for standard mounting rails and |
Grey | JWD1-4 | |
Blue | JWD1-4 BU | ||
(1) End plate: One additional piece must be attached to the end of each terminal strip set. If it is mounted in the center of the terminal strip, the creepage distance may increase. |
Grey | 2.5-10G | |
Blue | 2.5-10G BU | ||
(2) Central liaison part: It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will. |
ZL6/10 | Imax: 32 A | |
(3) Connecting sheet: For central connection of more than 10 digits |
LJ6/2 | ||
(4) Edge liaison part: Its role is the same as that of the central liaison part (2); with insulation on the back side; 10 digits that can be further divided at will |
2 digits: | BL6/2 | |
3 digits: | BL6/3 | ||
10 digits: | BL6/10 | ||
(5) Jumping liaison part: With the spacer (6), it can connect any non-adjacent terminals in the center to form a jumping liaison terminal group. |
KL6/10 | ||
(6) Spacer: Used as a spacer block between the accessory of the jumping liaison part (5) and the conductive part of the terminal |
K6 | ||
(7) Switch liaison part: To be used on top of the terminal for switch connection; the end plate (1) should be added between the connected terminals to ensure electrical isolation. |
|||
(8) Divider: It is used to separate two adjacent liaison terminal groups and can be inserted after assembly, without any effect on the overall space. |
GP | ||
(9) Group partition: (thickness: 1.5) Used for separation of each terminal group; with dual effects (visible grouping and electrical isolation) |
1.5-16 GF | ||
(10) Warning sign: Yellow warning mark on top of the terminal |
4 JS | ||
(11) Tag: It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will); it is white. |
ZP6 |
Terminal dimensions | ||
Thickness / width / end plate thickness | [mm] | 6.2/42.5/1.8 |
Height (TH 35:7.5 / TH 35:15 / G 32:15) | [mm] | 47/54.5/52 |
Technical data based on IEC/DIN VDE standards | ||
Maximum rated working current / cross-sectional area | [A] / [mm2] | 15128 |
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is used: | [mm2] | 45386 |
Rated impulse withstand voltage / degree of pollution | [kV]/- | 45507 |
Over-voltage category / insulation material group | -/- | lll/l |
Connection capacity | ||
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal | [mm2] | 0.25-4/0.25-4 |
Connection of multiple conductors (two conductors with the same cross-sectional area) | ||
Rigid conductor / flexible conductor | [mm2] | 0.2-1.5/0.2-1.5 |
Flexible conductor with tubular bare terminal | [mm2] | 0.25-1.5 |
Flexible conductor with DEV-tubular pre-insulated terminal | [mm2] | 0.5-2.5 |
Stripping length | [mm] | 8 |
Screw type | M3 | |
Torque | [Nm] | 0.6-0.8 |
Insulation material type | PA | |
Material flammability according to UL94 | V0 | |
Rated working voltage / rated working current / wire gauge | UL: [V]/[A]/AWG | 600/30/30-10 |