Terminal thickness: 5.2 | ||
Rigid conductor | Flexible conductor | |
(mm2) | ||
IEC 60947-7-2 | 0.2-4 | 0.2-2.5 |
Products Category
JWD1-2.5JD Screw Type General Din-Rail TB
Product Description
Parameters
Certification
Description |
Type |
||
Ground terminal: The yellow-green insulating housings can be mounted on the mounting rails |
JWD1-2.5 JD |
||
Edge liaison part: Its role is the same as that of the central liaison part (2); with insulation on the back side; 10 digits that can be further divided at will |
2 digits: |
BL5/2 |
|
3 digits: |
BL5/3 |
||
10 digits: |
BL5/10 |
||
Tag: It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will); it is white. |
ZP5 |
Terminal dimensions |
||
Thickness / width |
[mm] |
5.2/42.5 |
Height (TH 35:7.5 / TH 35:15 / G 32:15) |
[mm] |
47/54.5/52 |
Technical data based on IEC/DIN VDE standards |
|
|
Rated impulse withstand voltage / degree of pollution |
[kV]/- |
8/3’) |
Over-voltage category / insulation material group |
-/- |
III/I |
Connection capacity |
|
|
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal |
[mm2] |
0.25 -2.5/0.25-1.5 |
Connection of multiple conductors (two conductors with the same cross-sectional area) |
|
|
Rigid conductor / flexible conductor |
[mm2] |
0.2 -1.5/0.2-1.5 |
Flexible conductor with tubular bare terminal |
[mm2] |
0.25-1.5 |
Flexible conductor with DEV-tubular pre-insulated terminal |
[mm2] |
0.5-1.5 |
Stripping length |
[mm] |
8 |
Screw for terminal position: screw type / torque |
-/[Nm] |
M 3 / 0.6-0.8 |
Central fastening screw: screw type / torque |
-/[Nm] |
M 2.5/0.5-0.6 |
Insulation material type |
|
PA |
Material flammability according to UL94 |
|
V0 |
Rated working voltage / rated working current / wire gauge |
UL:[V]/[A]/AWG |
-/-/28-12 |
Note: When an edge liaison part is used, a cable below 1.5 mm2 should be used for a 2.5 mm2 terminal; corresponding cables should be used for terminals with other cross-sectional areas (mm2). |
1) If this terminal is adjacent to a feed-through terminal with the same configuration, and the voltage is greater than 690 V, one end plate must be inserted. |