Terminal thickness: 12.2 | ||||
Rigid conductor | Flexible conductor | I | Ui | |
(mm2) | (A) | (V) | ||
IEC 60947-7-1 | 2.5-25 | 4-16 | 101 | 800 |
Products Category
JWD1-16 Screw Type General Din-Rail TB
Product Description
Parameters
Certification
Description |
Color |
Type |
||
Terminal: With general-purpose locating base, suitable for standard mounting rails and |
Grey |
JWD1-16 |
||
Blue |
JWD1-16 BU |
|||
(1) End plate: One additional piece must be attached to the end of each terminal strip set. If it is mounted in the center of the terminal strip, the creepage distance may increase. |
Grey |
16G |
||
Blue |
16G BU |
|||
(2) Central liaison part: It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will. |
|
|
||
ZL10/12 |
Imax: 101 A |
|||
|
|
|||
(3) Connecting sheet: For central connection of more than 10 digits |
LJ12/2 |
|||
(4) Stepped central switchover part For switchover from ZL6/10 to ZL10/10 For switchover from ZL6/10 to ZL15/10 |
|
|||
(5) Edge liaison part: Its role is the same as that of the central liaison part (2); with insulation on the back side; 10 digits that can be further divided at will |
2 digits: |
BL12/2 |
||
3 digits: |
BL12/3 |
|||
10 digits: |
BL12/10 |
|||
(6) Jumping liaison part: With the spacer (7), it can connect any non-adjacent terminals in the center to form a jumping liaison terminal group. |
|
|||
(7) Spacer: Used as a spacer block between the accessory of the jumping liaison part (6) and the conductive part of the terminal |
|
|||
(8) Switch liaison part: To be used on top of the terminal for switch connection; based on the required breaking clearance, use a short or long overlapping strap. |
|
|||
(9) Divider: It is used to separate two adjacent liaison terminal groups and can be inserted after assembly, without any effect on the overall space. |
GP |
|||
(10) Group partition: (thickness: 1.5) Used for separation of each terminal group; with dual effects (visible grouping and electrical isolation) |
1.5-16 GF |
|||
(11) Warning sign: Yellow warning mark on top of the terminal |
16JS |
|||
(12) Tag: It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will); it is white. |
ZP10 |
Terminal dimensions |
|
|
Thickness / width / end plate thickness |
[mm] |
12.2/42.5/1.5 |
Height (TH 35:7.5 / TH 35:15 / G 32:15) |
[mm] |
54/61.5/59 |
Technical data based on IEC/DIN VDE standards |
|
|
Maximum rated working current / cross-sectional area |
[A] / [mm2] |
101/25 |
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is used: |
[mm2] |
16/16 |
Rated impulse withstand voltage / degree of pollution |
[kV]/- |
8/3 |
Over-voltage category / insulation material group |
-/- |
lll/l |
Connection capacity |
|
|
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal |
[mm2] |
1.5-16/1.5-16 |
Connection of multiple conductors (two conductors with the same cross-sectional area) |
|
|
Rigid conductor / flexible conductor |
[mm2] |
1.5-6/1.5-4 |
Flexible conductor with tubular bare terminal |
[mm2] |
1.5-6 |
Flexible conductor with DEV-tubular pre-insulated terminal |
[mm2] |
0.75-10 |
Stripping length |
[mm] |
11 |
Screw type |
|
M4 |
Torque |
[Nm] |
1.5-1.8 |
Insulation material type |
|
PA |
Material flammability according to UL94 |
|
V0 |
Rated working voltage / rated working current / wire gauge |
UL: [V]/[A]/AWG |
600/85/22-4 |