Terminal thickness: 8.2 | |||||
Rigid conductor | Flexible conductor | I | Ui | ||
(mm2) | (A) | (V) | |||
IEC 60 947-7-3 Used as a terminal for breaking capacity | 0.2-4 | 0.2-4 | 6.3* | 800 | |
With fuse | 0.2-4 | 0.2-4 | Note 1) |
Products Category
JWD1-10RD Screw Type Fuse Din-Rail TB
- The JWDI-10RD fuse terminal is designed for the fuses with or without the fuse identification, and with the specification of 6.3x32 mm. It can be connected with the ZL12/… central liaison part. The fuse will be mounted in the nut and both will be screwed into the terminal. The terminal type with luminous display is available. The display signal will be sent when the fuse is blown.
- If Type G fuse is used, refer to the IECI27-6 standard.
Product Description
Parameters
Certification
Description |
Schematic diagram |
Type |
Part Number |
Package quantity |
|||||
This fuse terminal can be mounted on the standard mounting rails and and can be equipped with a fuse tube (see Page 43 for details). |
|
JWD1-4RD (R055) |
5 574 141 |
25 |
|||||
Terminal with indicator lamp: (the same function as above) |
Voltage (AC / DC) |
Current |
|
|
|
||||
Terminal with indicator lamp: (the same function as above) |
24V-48V-110V, common for AC / DC |
2-3mmA |
JWD1-4RD/24V-110V AC/DC |
5 574 143 |
25 |
||||
Terminal with indicator lamp: (the same function as above) |
5V-12V, common for AC / DC |
1.8-9mmA |
JWD1-4RD/5V-12V AC/DC |
5 574 145 |
25 |
||||
Terminal with indicator lamp: (the same function as above) |
220V-380V, common for AC / DC |
1.6-4mmA |
JWD1-4RD/220V-380V AC/DC |
5 574 184 |
25 |
||||
(1) Central liaison part: It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will. |
|
|
|
|
|||||
(2) Connecting sheet For central connection of more than 10 digits |
|
|
|
|
|||||
(3) Edge liaison part: Its role is the same as that of the central liaison part; with insulation on the back side; 10 digits that can be further divided at will |
2 digits: |
|
BLS 8/2 |
8 582 182 |
100 |
||||
|
3 digits: |
|
BLS 8/3 |
8 582 183 |
100 |
||||
|
10 digits: |
|
BLS 8/10 |
8 582 190 |
50 |
||||
(4) Connecting strip: Used for coupling linkage of the hinge break-away arm |
|
4RD/LT |
8 824 101 |
|
|||||
(5) Tag: It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will). |
White |
|
ZP8 |
8 868 104 |
100 |
||||
Terminal dimensions |
|
|
|||||||
Thickness / width / end plate thickness |
[mm] |
8.2 / 72.5 |
|||||||
Height (TH 35:7.5 / TH 35:15 / G 32:15) |
[mm] |
56.5/64/61.5 |
|||||||
Technical data based on IEC/DIN VDE standards |
|
|
|||||||
Fuse type / dimensions & specifications |
-/ [mm] |
(See Page 42 for details.) |
|||||||
Maximum power consumption at 23 °C based on the E DIN VDE 0611-6: 1995-05 standard |
|
Note 1) |
|||||||
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is used |
[mm2] |
4/4 |
|||||||
Rated impulse withstand voltage / degree of pollution |
[kV]/- |
6/3 |
|||||||
Over-voltage category / insulation material group |
-/- |
III /1 |
|||||||
Connection capacity |
[mm2] |
|
|||||||
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal |
|
0.25-4 / 0.25-4 |
|||||||
Connection of multiple conductors (connecting two conductors with the same cross-sectional area) |
[mm2] |
|
|||||||
Rigid conductor / flexible conductor |
[mm2] |
0.2-4/0.2-4 |
|||||||
Flexible conductor with tubular bare terminal |
[mm2] |
0.25-4 |
|||||||
Flexible conductor with DEV-tubular pre-insulated terminal |
[mm] |
0.5-2.5 |
|||||||
Stripping length |
|
8 |
|||||||
Screw type |
[Nm] |
M3 |
|||||||
Torque |
[mm] |
0.6-0.8 |
|||||||
Insulation material type |
|
PA |
|||||||
Material flammability according to UL94 |
|
V0 |
|||||||
Rated working voltage / rated working current / wire gauge |
UL:[V]/[A]/AWG |
800/6.3/26-10 |
|||||||
Type G cartridge fuse-link with cylindrical cap ("Fuse Tube" for short) Fuse terminals with indicator lamp for special voltages can be customized upon the customer's request. |
|
Note 1): Current subject to the fuse tube, and voltage subject to the indicator lamp |